Network Appliance NS0-094 Practice Test 8

Question 70

A planning worksheet for Cabinet-16 has independently fed redundant power paths A and B. Each path, if it is the sole surviving path, can supply up to 2500 W and 2275 W respectively. The protected modeled load is 1950 W. Ignore transient inrush and apply this simplified capacity model only. Which THREE statements correctly follow from the scenario?

  1. Claim actual hardware is validated solely by this arithmetic
  2. Either-feed limit is 2275 W
  3. Feed B margin is 325 W
  4. Feed A margin is 550 W
  5. Ignore the 1950 W protected load
  6. Use 4775 W as single-feed capacity

Explanation

Correct Answers

B:

The smaller of the independently surviving capacities governs the condition.

C:

2275−1950=325.

D:

2500−1950=550.

Incorrect Answers

A:

A real system also requires model-specific support and operational verification.

E:

The surviving feed must carry that load.

F:

This is the sum of two feeds, not one.

Question 71

A planning worksheet for Cabinet-17 has independently fed redundant power paths A and B. Each path, if it is the sole surviving path, can supply up to 2700 W and 2450 W respectively. The protected modeled load is 2140 W. Ignore transient inrush and apply this simplified capacity model only. What is the margin on surviving feed A if B fails?

  1. 2700 W
  2. 310 W
  3. 4840 W
  4. 560 W

Explanation

Correct Answer

D:

2700 W capacity minus 2140 W modeled load leaves 560 W.

Incorrect Answers

A:

The protected load still consumes capacity.

B:

That is the margin for feed B.

C:

Load must be subtracted, not added.

Question 72

A planning worksheet for Cabinet-17 has independently fed redundant power paths A and B. Each path, if it is the sole surviving path, can supply up to 2700 W and 2450 W respectively. The protected modeled load is 2140 W. Ignore transient inrush and apply this simplified capacity model only. What is the margin on surviving feed B if A fails?

  1. 560 W
  2. 310 W
  3. 4590 W
  4. 2450 W

Explanation

Correct Answer

B:

2450−2140=310 W.

Incorrect Answers

A:

That is the margin on A.

C:

The load reduces available margin.

D:

This omits the protected load.

Question 73

A planning worksheet for Cabinet-17 has independently fed redundant power paths A and B. Each path, if it is the sole surviving path, can supply up to 2700 W and 2450 W respectively. The protected modeled load is 2140 W. Ignore transient inrush and apply this simplified capacity model only. What is the largest modeled load that either surviving feed alone could support?

  1. 2450 W
  2. 2140 W
  3. 5150 W
  4. 2700 W

Explanation

Correct Answer

A:

For either single-feed failure, the smaller capacity (2450 W) determines the limit.

Incorrect Answers

B:

The current load is not the maximum modeled capacity.

C:

Combined capacity is not available when only one feed survives.

D:

This only fits the larger feed.

Question 74

A planning worksheet for Cabinet-17 has independently fed redundant power paths A and B. Each path, if it is the sole surviving path, can supply up to 2700 W and 2450 W respectively. The protected modeled load is 2140 W. Ignore transient inrush and apply this simplified capacity model only. Does the current modeled load fit either single-feed survival condition?

  1. Yes, using the smaller feed capacity of 2450 W
  2. Treat 2700 W as the limit in both failure cases
  3. Assume physical redundancy guarantees no service interruption
  4. Add the feeds and ignore failure conditions

Explanation

Correct Answer

A:

2140 W is at or below the smaller capacity; both modeled survival cases fit.

Incorrect Answers

B:

The smaller surviving feed could be the constrained path.

C:

A capacity worksheet does not establish actual failover or model-specific service behavior.

D:

The worksheet asks whether either feed alone can carry the load.

Question 75

A planning worksheet for Cabinet-17 has independently fed redundant power paths A and B. Each path, if it is the sole surviving path, can supply up to 2700 W and 2450 W respectively. The protected modeled load is 2140 W. Ignore transient inrush and apply this simplified capacity model only. Which TWO statements correctly follow from the scenario?

  1. Claim actual hardware is validated solely by this arithmetic
  2. Feed B margin is 310 W
  3. Ignore the 2140 W protected load
  4. Feed A margin is 560 W
  5. Use 5150 W as single-feed capacity

Explanation

Correct Answers

B:

2450−2140=310.

D:

2700−2140=560.

Incorrect Answers

A:

A real system also requires model-specific support and operational verification.

C:

The surviving feed must carry that load.

E:

This is the sum of two feeds, not one.

Question 76

A planning worksheet for Cabinet-18 has independently fed redundant power paths A and B. Each path, if it is the sole surviving path, can supply up to 2900 W and 2625 W respectively. The protected modeled load is 2330 W. Ignore transient inrush and apply this simplified capacity model only. What is the margin on surviving feed A if B fails?

  1. 5230 W
  2. 2900 W
  3. 570 W
  4. 295 W

Explanation

Correct Answer

C:

2900 W capacity minus 2330 W modeled load leaves 570 W.

Incorrect Answers

A:

Load must be subtracted, not added.

B:

The protected load still consumes capacity.

D:

That is the margin for feed B.

Question 77

A planning worksheet for Cabinet-18 has independently fed redundant power paths A and B. Each path, if it is the sole surviving path, can supply up to 2900 W and 2625 W respectively. The protected modeled load is 2330 W. Ignore transient inrush and apply this simplified capacity model only. What is the margin on surviving feed B if A fails?

  1. 570 W
  2. 2625 W
  3. 4955 W
  4. 295 W

Explanation

Correct Answer

D:

2625−2330=295 W.

Incorrect Answers

A:

That is the margin on A.

B:

This omits the protected load.

C:

The load reduces available margin.

Question 78

A planning worksheet for Cabinet-18 has independently fed redundant power paths A and B. Each path, if it is the sole surviving path, can supply up to 2900 W and 2625 W respectively. The protected modeled load is 2330 W. Ignore transient inrush and apply this simplified capacity model only. What is the largest modeled load that either surviving feed alone could support?

  1. 2625 W
  2. 2330 W
  3. 2900 W
  4. 5525 W

Explanation

Correct Answer

A:

For either single-feed failure, the smaller capacity (2625 W) determines the limit.

Incorrect Answers

B:

The current load is not the maximum modeled capacity.

C:

This only fits the larger feed.

D:

Combined capacity is not available when only one feed survives.

Question 79

A planning worksheet for Cabinet-18 has independently fed redundant power paths A and B. Each path, if it is the sole surviving path, can supply up to 2900 W and 2625 W respectively. The protected modeled load is 2330 W. Ignore transient inrush and apply this simplified capacity model only. Does the current modeled load fit either single-feed survival condition?

  1. Assume physical redundancy guarantees no service interruption
  2. Yes, using the smaller feed capacity of 2625 W
  3. Add the feeds and ignore failure conditions
  4. Treat 2900 W as the limit in both failure cases

Explanation

Correct Answer

B:

2330 W is at or below the smaller capacity; both modeled survival cases fit.

Incorrect Answers

A:

A capacity worksheet does not establish actual failover or model-specific service behavior.

C:

The worksheet asks whether either feed alone can carry the load.

D:

The smaller surviving feed could be the constrained path.

Question 80

A planning worksheet for Cabinet-18 has independently fed redundant power paths A and B. Each path, if it is the sole surviving path, can supply up to 2900 W and 2625 W respectively. The protected modeled load is 2330 W. Ignore transient inrush and apply this simplified capacity model only. Which THREE statements correctly follow from the scenario?

  1. Either-feed limit is 2625 W
  2. Claim actual hardware is validated solely by this arithmetic
  3. Feed B margin is 295 W
  4. Feed A margin is 570 W
  5. Use 5525 W as single-feed capacity
  6. Ignore the 2330 W protected load

Explanation

Correct Answers

A:

The smaller of the independently surviving capacities governs the condition.

C:

2625−2330=295.

D:

2900−2330=570.

Incorrect Answers

B:

A real system also requires model-specific support and operational verification.

E:

This is the sum of two feeds, not one.

F:

The surviving feed must carry that load.

NetApp Hardware Support Engineer Professional (NS0-094) Practice Tests

UP

SPECIAL OFFER: GET 10% OFF

This is ONE TIME OFFER

ExamSnap Discount Offer
Enter Your Email Address to Receive Your 10% Off Discount Code

A confirmation link will be sent to this email address to verify your login. *We value your privacy. We will not rent or sell your email address.

Download Free Demo of VCE Exam Simulator

Experience Avanset VCE Exam Simulator for yourself.

Simply submit your e-mail address below to get started with our interactive software demo of your free trial.

Free Demo Limits: In the demo version you will be able to access only first 5 questions from exam.