Question 60

A planning worksheet for Cabinet-14 has independently fed redundant power paths A and B. Each path, if it is the sole surviving path, can supply up to 2100 W and 1925 W respectively. The protected modeled load is 1570 W. Ignore transient inrush and apply this simplified capacity model only. Which THREE statements correctly follow from the scenario?

  1. Ignore the 1570 W protected load
  2. Either-feed limit is 1925 W
  3. Claim actual hardware is validated solely by this arithmetic
  4. Feed B margin is 355 W
  5. Use 4025 W as single-feed capacity
  6. Feed A margin is 530 W

Explanation

Correct Answers

B:

The smaller of the independently surviving capacities governs the condition.

D:

1925−1570=355.

F:

2100−1570=530.

Incorrect Answers

A:

The surviving feed must carry that load.

C:

A real system also requires model-specific support and operational verification.

E:

This is the sum of two feeds, not one.

Question 61

A planning worksheet for Cabinet-15 has independently fed redundant power paths A and B. Each path, if it is the sole surviving path, can supply up to 2300 W and 2100 W respectively. The protected modeled load is 1760 W. Ignore transient inrush and apply this simplified capacity model only. What is the margin on surviving feed A if B fails?

  1. 4060 W
  2. 2300 W
  3. 340 W
  4. 540 W

Explanation

Correct Answer

D:

2300 W capacity minus 1760 W modeled load leaves 540 W.

Incorrect Answers

A:

Load must be subtracted, not added.

B:

The protected load still consumes capacity.

C:

That is the margin for feed B.

Question 62

A planning worksheet for Cabinet-15 has independently fed redundant power paths A and B. Each path, if it is the sole surviving path, can supply up to 2300 W and 2100 W respectively. The protected modeled load is 1760 W. Ignore transient inrush and apply this simplified capacity model only. What is the margin on surviving feed B if A fails?

  1. 340 W
  2. 2100 W
  3. 3860 W
  4. 540 W

Explanation

Correct Answer

A:

2100−1760=340 W.

Incorrect Answers

B:

This omits the protected load.

C:

The load reduces available margin.

D:

That is the margin on A.

Question 63

A planning worksheet for Cabinet-15 has independently fed redundant power paths A and B. Each path, if it is the sole surviving path, can supply up to 2300 W and 2100 W respectively. The protected modeled load is 1760 W. Ignore transient inrush and apply this simplified capacity model only. What is the largest modeled load that either surviving feed alone could support?

  1. 1760 W
  2. 2100 W
  3. 2300 W
  4. 4400 W

Explanation

Correct Answer

B:

For either single-feed failure, the smaller capacity (2100 W) determines the limit.

Incorrect Answers

A:

The current load is not the maximum modeled capacity.

C:

This only fits the larger feed.

D:

Combined capacity is not available when only one feed survives.

Question 64

A planning worksheet for Cabinet-15 has independently fed redundant power paths A and B. Each path, if it is the sole surviving path, can supply up to 2300 W and 2100 W respectively. The protected modeled load is 1760 W. Ignore transient inrush and apply this simplified capacity model only. Does the current modeled load fit either single-feed survival condition?

  1. Add the feeds and ignore failure conditions
  2. Assume physical redundancy guarantees no service interruption
  3. Treat 2300 W as the limit in both failure cases
  4. Yes, using the smaller feed capacity of 2100 W

Explanation

Correct Answer

D:

1760 W is at or below the smaller capacity; both modeled survival cases fit.

Incorrect Answers

A:

The worksheet asks whether either feed alone can carry the load.

B:

A capacity worksheet does not establish actual failover or model-specific service behavior.

C:

The smaller surviving feed could be the constrained path.

Question 65

A planning worksheet for Cabinet-15 has independently fed redundant power paths A and B. Each path, if it is the sole surviving path, can supply up to 2300 W and 2100 W respectively. The protected modeled load is 1760 W. Ignore transient inrush and apply this simplified capacity model only. Which TWO statements correctly follow from the scenario?

  1. Claim actual hardware is validated solely by this arithmetic
  2. Ignore the 1760 W protected load
  3. Feed A margin is 540 W
  4. Feed B margin is 340 W
  5. Use 4400 W as single-feed capacity

Explanation

Correct Answers

C:

2300−1760=540.

D:

2100−1760=340.

Incorrect Answers

A:

A real system also requires model-specific support and operational verification.

B:

The surviving feed must carry that load.

E:

This is the sum of two feeds, not one.

Question 66

A planning worksheet for Cabinet-16 has independently fed redundant power paths A and B. Each path, if it is the sole surviving path, can supply up to 2500 W and 2275 W respectively. The protected modeled load is 1950 W. Ignore transient inrush and apply this simplified capacity model only. What is the margin on surviving feed A if B fails?

  1. 550 W
  2. 4450 W
  3. 2500 W
  4. 325 W

Explanation

Correct Answer

A:

2500 W capacity minus 1950 W modeled load leaves 550 W.

Incorrect Answers

B:

Load must be subtracted, not added.

C:

The protected load still consumes capacity.

D:

That is the margin for feed B.

Question 67

A planning worksheet for Cabinet-16 has independently fed redundant power paths A and B. Each path, if it is the sole surviving path, can supply up to 2500 W and 2275 W respectively. The protected modeled load is 1950 W. Ignore transient inrush and apply this simplified capacity model only. What is the margin on surviving feed B if A fails?

  1. 4225 W
  2. 325 W
  3. 2275 W
  4. 550 W

Explanation

Correct Answer

B:

2275−1950=325 W.

Incorrect Answers

A:

The load reduces available margin.

C:

This omits the protected load.

D:

That is the margin on A.

Question 68

A planning worksheet for Cabinet-16 has independently fed redundant power paths A and B. Each path, if it is the sole surviving path, can supply up to 2500 W and 2275 W respectively. The protected modeled load is 1950 W. Ignore transient inrush and apply this simplified capacity model only. What is the largest modeled load that either surviving feed alone could support?

  1. 2275 W
  2. 4775 W
  3. 1950 W
  4. 2500 W

Explanation

Correct Answer

A:

For either single-feed failure, the smaller capacity (2275 W) determines the limit.

Incorrect Answers

B:

Combined capacity is not available when only one feed survives.

C:

The current load is not the maximum modeled capacity.

D:

This only fits the larger feed.

Question 69

A planning worksheet for Cabinet-16 has independently fed redundant power paths A and B. Each path, if it is the sole surviving path, can supply up to 2500 W and 2275 W respectively. The protected modeled load is 1950 W. Ignore transient inrush and apply this simplified capacity model only. Does the current modeled load fit either single-feed survival condition?

  1. Add the feeds and ignore failure conditions
  2. Treat 2500 W as the limit in both failure cases
  3. Yes, using the smaller feed capacity of 2275 W
  4. Assume physical redundancy guarantees no service interruption

Explanation

Correct Answer

C:

1950 W is at or below the smaller capacity; both modeled survival cases fit.

Incorrect Answers

A:

The worksheet asks whether either feed alone can carry the load.

B:

The smaller surviving feed could be the constrained path.

D:

A capacity worksheet does not establish actual failover or model-specific service behavior.

Question 70

A planning worksheet for Cabinet-16 has independently fed redundant power paths A and B. Each path, if it is the sole surviving path, can supply up to 2500 W and 2275 W respectively. The protected modeled load is 1950 W. Ignore transient inrush and apply this simplified capacity model only. Which THREE statements correctly follow from the scenario?

  1. Claim actual hardware is validated solely by this arithmetic
  2. Either-feed limit is 2275 W
  3. Feed B margin is 325 W
  4. Feed A margin is 550 W
  5. Ignore the 1950 W protected load
  6. Use 4775 W as single-feed capacity

Explanation

Correct Answers

B:

The smaller of the independently surviving capacities governs the condition.

C:

2275−1950=325.

D:

2500−1950=550.

Incorrect Answers

A:

A real system also requires model-specific support and operational verification.

E:

The surviving feed must carry that load.

F:

This is the sum of two feeds, not one.

NetApp Hardware Support Engineer Professional (NS0-094) Practice Tests

UP

SPECIAL OFFER: GET 10% OFF

This is ONE TIME OFFER

ExamSnap Discount Offer
Enter Your Email Address to Receive Your 10% Off Discount Code

A confirmation link will be sent to this email address to verify your login. *We value your privacy. We will not rent or sell your email address.

Download Free Demo of VCE Exam Simulator

Experience Avanset VCE Exam Simulator for yourself.

Simply submit your e-mail address below to get started with our interactive software demo of your free trial.

Free Demo Limits: In the demo version you will be able to access only first 5 questions from exam.